• >UL listed for copper-bonded, galvanized, and stainless steel ground rods.
  • UL listed for #4, #5 and #6 rebar.
  • UL listed for direct burial in earth and concrete with a stainless steel bolt.
  • Performs the functions of economy, standard duty, heavy duty, and extra heavy duty.
  • Able to withstand torque in excess of UL 467 requirements of 150 in/lb
  • RUS listed.
  • Made in USA. 
ONE CLAMP FITS 1/2, 5/8 AND 3/4 ROD DIAMETERS.
CATALOG NUMBERGround Rod
Size, Inches
Rod Diameter Metric (Approx.)Rebar SizeWire Range AWG No. (CU)Carton & Master PackWt. Per
100 lb (kg)
NAED UPC
No.632591-
SRC1/2 (0.500) to 3/4 (0.75) For Copper-Bonded, Galvanized and Stainless Steel12.8 mm to 17.3 mm#4 (1/2 inch)
#5 (5/8 inch), #6 (3/4 inch)
10 AWG - 1/050/40016 (7.3)61344-6
SRC3/4 F (0.750 - 0.765) Full Size Galvanized19.1 mm10 AWG Solid - 2 AWG Solid, 8 AWG Stranded - 1 AWG Stranded
  • UL listed for copper-bonded, galvanized and stainless steel ground rod stamped on the clamp.
  • UL listed for #4 1/2-inch rebar.
  • UL listed for direct burial in earth and concrete with a stainless steel bolt.
  • Cast copper alloy body with hex head bolt provides simple trouble-free connection at low cost.
  • Able to withstand torque in excess of UL 467 requirements of 150 in/lb.
  • Made in USA. 
CATALOG NUMBERGround Rod Size, InchesRod Diameter Metric (Approx.)Rebar SizeWire Range AWG No. (CU)Carton & Master PackWt. per
100 lb (kg)
NAED
UPC
No.632591-
G-51/2 (0.500) to 5/8 (0.625) For Copper-Bonded, Galvanized and Stainless Steel12.8 mm to 15.9 mm#4 (1/2 inch)10 AWG - 2 AWG50/40010 (4.5)70708-4
G-55/8 UL Galvanized (0.539 to 0.555)14.2 mm10 AWG - 2 AWG
G-55/8 F Full Size Galvanized (0.625 - 0.640)15.9 mm10 AWG Solid- 2 AWG Solid, 10 AWG Stranded-
3 AWG Stranded
Catalog
Number
Rod
Diameter
Rod Diameter
(metric) Approximate
Conductor
Range
Sub &
Master Pack
Wt. per
100 lb (kg)
NAED
UPC
No.632591-
G-3 (Non UL)3/8"9.5 mm4 Str. - 10 Sol.100 / 8006 (2.7)70706-0
G-4*(Use G-5)1/2"12.8 mm2 Str. - 10 Sol.100 / 8009 (4.1)70707-7
G-6*(Use SRC)3/4"17.3 mm2 Str. - 10 Sol.50 / 40011 (5.0)70709-1

*-These items UL and CSA Listed in US and Canada for direct burial in earth and concrete.-The G-6 fits all 3/4-inch diameter rods regardless of actual or nominal diameter.

SRC-SS Stainless Steel Universal Ground Rod Clamp

  • Made from 301 stainless steel
  • UL-Listed and marked for copper-bonded, galvanized, and stainless steel ground rods; also for #4, #5 and #6 (1/2″, 5/8″ and 3/4″) rebar
  • UL-Listed in US and Canada for direct burial in earth and concrete
  • One size fits all
  • Patent pending
  • Made in USA. 
One Clamp Fits 3/8, 1/2, 5/8 and 3/4 Rod Diameters.
Catalog
Number
Rod
Diameter
Rod Diameter
(metric) Approximate
Conductor
Range
Sub &
Master Pack
Wt. per
100 lb (kg)
NAED UPC
No.632591-
SRC-SS3/8", 1/2", 5/8", 3/4"9.5 mm, 12.8 mm, 14.2 mm, 17.3 mm1/0 Str. - 10 Sol.1009 (4.1)61499-3

Note: When used with stainless steel ground rods, the wire range is #8 solid to #2 stranded.

Ground Rod Clamps (Hex-Head Tin-Plated)

  • Bronze alloy or stainless steel hardware approved for direct burial in earth and concrete
  • Cast copper alloy body tin-plated with hex head bolt provides simple trouble-free connection at low cost on galvanized ground rods
  • Made in USA. 
Catalog
Number
Rod
Diameter
Rod Diameter
(metric) Approximate
Conductor
Range
Sub &
MasterPack
Wt. per
100 lb (kg)
NAED
UPC
No.632591-
G3P (Non UL)3/8"9.5 mm4 Str. - 10 Sol.100 / 8006 (2.7)61135-0
G4P*1/2"12.8 mm2 Str. - 10 Sol.100 / 8009 (4.1)61219-7
G5P*5/8"-1/2"12.8 mm to 14.2 mm2 Str. - 10 Sol.50 / 40010 (4.5)61220-3
G6P*3/4"17.3 mm2 Str. - 10 Sol.50 / 40011 (5.0)61221-0

* RUS Listed and marked per RUS specification and traceability.

Heavy-Duty Ground Rod Clamps (Hex-Head)

  • Bronze alloy or stainless steel hardware both UL listed approved for direct burial in earth and concrete.
  • Ground connection is secured by long bearing surface of clamp on ground wire.
  • High-strength corrosion-resistant copper alloy. All Heavy Duty clamps UL Listed for direct burial in earth and concrete.
  • UL listed for copper-bonded, galvanized and stainless steel ground rods.
  • Made in USA. 
Catalog
Number
Rod
Diameter
Rod Diameter
(metric) Approximate
Conductor
Range
Sub &
Master Pack
Wt. per
100 lb (kg)
NAED
UPC
No.632591-
JAB12H1/2"12.8 mm2 Str. - 10 Sol.100 / 80012 (5.4)70715-2
JAB58H5/8"14.2 mm1/0 Str. - 8 Sol.50 / 40013 (5.9)70716-9
JAB58HH*5/8"14.2 mm1/0 Str. - 8 Sol.50 / 40014 (6.4)61311-8
JAB58HP5/814.2 mm1/0 Str. - 8 Sol.50 / 40013 (5.9)61502-0
JAB34H3/4"17.3 mm1/0 Str. - 8 Sol.25 / 25015 (6.8)70717-6
JAB34HH3/4"17.3 mm3/0 Str. - 8 Sol.25/ 20017 (7.7)61495-5
JAB1H1"25.4 mm4/0 Str. - 8 Sol.50 / 40025 (11.3)70718-3

*-HH represents “Heavy duty hex head design screw 1/2” – 13 threads with 9/16” hex head-These items UL and CSA Listed except for JAB58HH and JAB34HHJAB58H Listed for US and Canada – 7/16 -14 threads-P designates tin plated

Type DGC Drive-On Ground Clamp

Catalog
Number
Ground Rod
Diameter
Rod Diameter
(metric) Approximate
Pieces/
Cartons
WT/C
lb (kg)
Ground
Wire Size
NAED
UPC
No.632591-
DGC-5844*5/8 (0.555 - 0.565)14.2 mm5020 (9.1)1 or 2 - #4 Sol.61329-3
DGC-5866*5/8 (0.555 - 0.565)14.2 mm3020 (9.1)1 or 2 - #6 Sol.61330-9

• For use on all 5/8″ diameter UL Listed copper-bonded ground rods.
• Used to bond one or two, #4 or #6, solid copper conductors respectively.
• Produced from high-strength copper alloy, the same material as UL Listed “acorn” type ground rod clamps.
• May be used effectively for direct-burial applications.
• To install, the only required tool is a hammer. Compression forces maximize the “direct” surface-to-surface copper contact between conductor and ground rod electrode.
• A drive-head should be used during installation of the ground rod electrode into the soil, thus minimizing any possible mushrooming or deformation on the drive (or chamfer) end of the rod. This will improve ease of installation of the drive-on clamp.
• This design places the grounding conductor in “direct” contact with the ground rod, thereby eliminating multiple paths for the current to follow, which could contribute to increased resistance.

TO INSTALL:
• Select the proper connector from the above chart.
• Drive the ground rod electrode to the proper depth per national or local code recommendations.
• Position connector and ground rod conductors as shown in middle illustration.
• Drive connector onto rod until top of connector is flush with top of ground rod as shown in adjacent illustration. Galvan suggests using a 20-ounce hammer.